E3D-APAM-RPT-002 · Board Condition Report · Board 17 of 67
DB-D18N
Apron field-lighting board
AMBER — Defects logged
Status: Complete · Condition Index 17.5/100

1. Verdict & suitability

Assessment summary

Can house the new LED luminaires & controlsYES — universal
BasisLED load ≪ legacy HID; enclosure space & isolation adequate
Overall condition ratingAMBER — Defects logged
P2
0
P3
1
P4
2
Photos
12
0Condition Index 17.5100

Rated AMBER — Defects logged. The board can house the new LED works.

2. Location

N Apron boards · this board highlighted
GPS (lat, long)-37.667911, 144.843450
Zone / apronTo be confirmed against apron key-plan
Upstream source (parent DB / sub)To be confirmed against airfield reticulation drawings
Inspected21–22 June 2026

3. Supply & electrical

As-built supply and cabling recorded on site. Visual / physical condition audit only — no electrical testing performed.

Incoming supply & earthing
Supplied fromWestern Apron MSB
Upstream CB way(s)15
Phases3-phase
Line voltage400 V (L-L)
Phase-earth voltage230 V (L-N)
Earthing systemReticulated
Upstream protectionIsolator only (no OCPD confirmed at board)
Supply cable schedule
Active conductor size25 mm²
Configuration1x4C
Conductor arrangementcircular
Parallel sets1
Conductor materialCopper
Insulation / typePVC
ArmourUnarmoured
Installation methodUnderground Enclosure
Conduit100 mm
Loaded circuits in conduit—
Estimated depth—
Earth arrangementIntegral — 6 mm²
Approx. lengthNot recorded

4. Condition assessment

Scored per the Condition Scoring & Rating Model (six standards-referenced dimensions, 0–4 on the P-scale). Rating is gated — a single safety/structural P2 breach sets RED regardless of the averaged Index.

DimensionScoreGradeObservation
Electrical safety & compliance2Moderate (P3)Direct-contact / earthing / labelling integrity
Structural & enclosure integrity0None observedNone observed
Corrosion & protective coating1Minor (P4)Corrosion of fixings, bars and coatings; general fouling
Ingress protection0None observedNone observed
Access & working space0None observedNone observed
Thermal / fire & component0None observedNone observed
Rationale. Rated AMBER (Condition Index 17.5/100). The board shows minor, logged wear only.

5. Defects

Field-observed defect(s) for this board, itemised into discrete findings — each with its own priority and category.

RefCategoryDefectPri
D-01 Electrical Non-standard insulation on busbar combs P3
D-02 Housekeeping Internal dust / dirt accumulation P4
D-03 Corrosion Minor surface rust to fixings and bars P4

6. Suitability for the LED works

Suitability for LED worksYES

The new LED floodlight load and driver footprint are materially smaller than the legacy HID gear removed, and the existing 3-phase supply, 25 mm² feed and cabinet isolation are adequate for the new works. This conclusion is universal across the fleet and is independent of condition.

7. Photographic evidence

12 site photographs. Frames outlined in orange are keyed to a priority defect (fire, structural, access or ingress evidence).

Site photo
Site photo #1
Site photo
Site photo #2
Site photo
Site photo #3
Site photo
Site photo #4
Site photo
Site photo #5
Site photo
Site photo #6
Site photo
Site photo #7
Site photo
Site photo #8
Site photo
Site photo #9
Site photo
Site photo #10
Site photo
Site photo #11
Site photo
Site photo #12