E3D-APAM-RPT-002 · Board Condition Report · Board 20 of 67
DB-NthApron-NEss
Northern apron board
AMBER — Defects logged
Status: In_progress · Condition Index 20/100

1. Verdict & suitability

Assessment summary

Can house the new LED luminaires & controlsYES — universal
BasisLED load ≪ legacy HID; enclosure space & isolation adequate
Overall condition ratingAMBER — Defects logged
P2
0
P3
2
P4
1
Photos
10
0Condition Index 20100

Rated AMBER — Defects logged. The board can house the new LED works.

2. Location

N Apron boards · this board highlighted
GPS (lat, long)-37.667482, 144.845413
Zone / apronTo be confirmed against apron key-plan
Upstream source (parent DB / sub)To be confirmed against airfield reticulation drawings
Inspected21–22 June 2026

3. Supply & electrical

As-built supply and cabling recorded on site. Visual / physical condition audit only — no electrical testing performed.

Incoming supply & earthing
Supplied fromSub 42 LV MSB (Non-Essential)
Upstream CB way(s)Q39
Phases3-phase
Line voltage400 V (L-L)
Phase-earth voltage230 V (L-N)
Earthing systemUnknown
Upstream protectionNot confirmed
Supply cable schedule
Active conductor size95 mm²
Configuration4x1C
Conductor arrangementtrefoil
Parallel sets2
Conductor materialCopper
Insulation / typeXLPE
ArmourUnarmoured
Installation methodUnderground Enclosure
Conduit100 mm
Loaded circuits in conduit—
Estimated depth—
Earth arrangementSeparate — 35 mm²
Approx. lengthNot recorded

4. Condition assessment

Scored per the Condition Scoring & Rating Model (six standards-referenced dimensions, 0–4 on the P-scale). Rating is gated — a single safety/structural P2 breach sets RED regardless of the averaged Index.

DimensionScoreGradeObservation
Electrical safety & compliance0None observedNone observed
Structural & enclosure integrity2Moderate (P3)Enclosure & chassis mechanical integrity
Corrosion & protective coating2Moderate (P3)Corrosion of fixings, bars and coatings; general fouling
Ingress protection0None observedNone observed
Access & working space0None observedNone observed
Thermal / fire & component0None observedNone observed
Rationale. Rated AMBER (Condition Index 20/100). Field condition records corrosion to fixings and bars.

5. Defects

Field-observed defect(s) for this board, itemised into discrete findings — each with its own priority and category.

RefCategoryDefectPri
D-01 Corrosion Severe rust to door mechanism and enclosure P3
D-02 Housekeeping Internal dust / dirt accumulation P4
D-03 Corrosion Minor pitting to enclosure / structure P3

6. Suitability for the LED works

Suitability for LED worksYES

The new LED floodlight load and driver footprint are materially smaller than the legacy HID gear removed, and the existing 3-phase supply, 95 mm² feed and cabinet isolation are adequate for the new works. This conclusion is universal across the fleet and is independent of condition.

7. Photographic evidence

10 site photographs. Frames outlined in orange are keyed to a priority defect (fire, structural, access or ingress evidence).

Site photo
Site photo #1
Site photo
Site photo #2
Site photo
Site photo #3
Site photo
Site photo #4
Site photo
Site photo #5
Site photo
Site photo #6
Site photo
Site photo #7
Site photo
Site photo #8
Site photo
Site photo #9
Site photo
Site photo #10