E3D-APAM-RPT-002 · Board Condition Report · Board 64 of 67
DB-B26S
Apron field-lighting board
AMBER — Defects logged
Status: Complete · Condition Index 15/100

1. Verdict & suitability

Assessment summary

Can house the new LED luminaires & controlsYES — universal
BasisLED load ≪ legacy HID; enclosure space & isolation adequate
Overall condition ratingAMBER — Defects logged
P2
0
P3
2
P4
2
Photos
13
0Condition Index 15100

Rated AMBER — Defects logged. The board can house the new LED works.

2. Location

N Apron boards · this board highlighted
GPS (lat, long)-37.667435, 144.851824
Zone / apronTo be confirmed against apron key-plan
Upstream source (parent DB / sub)To be confirmed against airfield reticulation drawings
Inspected21–22 June 2026

3. Supply & electrical

As-built supply and cabling recorded on site. Visual / physical condition audit only — no electrical testing performed.

Incoming supply & earthing
Supplied fromSwitchboard Room 27
Upstream CB way(s)—
Phases3-phase
Line voltage400 V (L-L)
Phase-earth voltage230 V (L-N)
Earthing systemReticulated
Upstream protectionIsolator only (no OCPD confirmed at board)
Supply cable schedule
Active conductor size16 mm²
Configuration1x4C
Conductor arrangementcircular
Parallel sets1
Conductor materialCopper
Insulation / typePVC
ArmourUnarmoured
Installation methodUnderground Enclosure
Conduit100 mm
Loaded circuits in conduit1
Estimated depth0.5 m
Earth arrangementSeparate — 6 mm²
Approx. lengthNot recorded
Field note (open supply query): Supply: Switchboard Room 27 — resolve looped-vs-dedicated feed arrangement on the F-series 50 mm mains before finalising the outgoing design.

4. Condition assessment

Scored per the Condition Scoring & Rating Model (six standards-referenced dimensions, 0–4 on the P-scale). Rating is gated — a single safety/structural P2 breach sets RED regardless of the averaged Index.

DimensionScoreGradeObservation
Electrical safety & compliance0None observedNone observed
Structural & enclosure integrity0None observedNone observed
Corrosion & protective coating2Moderate (P3)Corrosion of fixings, bars and coatings; general fouling
Ingress protection2Moderate (P3)Sealing of penetrations against dust / water ingress
Access & working space0None observedNone observed
Thermal / fire & component0None observedNone observed
Rationale. Rated AMBER (Condition Index 15/100). Field condition records corrosion to fixings and bars and unsealed penetrations / ingress.

5. Defects

Field-observed defect(s) for this board, itemised into discrete findings — each with its own priority and category.

RefCategoryDefectPri
D-01 Housekeeping Internal dust / dirt accumulation P4
D-02 Corrosion Significant rust / corrosion to enclosure, fixings and bars P3
D-03 Corrosion Minor surface rust to fixings and bars P4
D-04 Ingress Unsealed cable penetrations at base / gland plate P3

6. Suitability for the LED works

Suitability for LED worksYES

The new LED floodlight load and driver footprint are materially smaller than the legacy HID gear removed, and the existing 3-phase supply, 16 mm² feed and cabinet isolation are adequate for the new works. This conclusion is universal across the fleet and is independent of condition.

7. Photographic evidence

13 site photographs. Frames outlined in orange are keyed to a priority defect (fire, structural, access or ingress evidence).

Site photo
Site photo #1
Site photo
Site photo #2
Site photo
Site photo #3
Site photo
Site photo #4
Site photo
Site photo #5
Site photo
Site photo #6
Site photo
Site photo #7
Site photo
Site photo #8
Site photo
Site photo #9
Site photo
Site photo #10
Site photo
Site photo #11
Site photo
Site photo #12
Site photo
Site photo #13